LOW PRESSURE TRANSMITTER PERITACT 2000-K10
Low pressure transmitter
Dynamic micro flow sensor
Smallest measuring range 0…10 Pa
Analog output 0…10 V and 0/4…20 mA
2 outputs with change-over contacts 250V, 8A
Characteristic linear or square-rooted
LCD-Display with 4 lines of 20 characters
Contact function min. or max.
Supply voltage 230 Vac, 24 Vac or 24 Vdc
Protection class IP 65
Manometer with diaphragm element for indication of pressure, under pressure or differential pressure of non aggressive gas. Thanks to the measuring principle, the device is irrespective of position and has an extremely high zero-point security with the smallest measuring ranges. Thereby, it is particularly suitable for air flow measurement according to the “Differential pressure” or “dynamic pressure” method with square-root characteristic. No negative pressure measurement possible.
Data sheet – Differential presure transmitter – PERITACT 2000 series
Operation manuals – PERITACT2000
Operating mode:
Measuring mode with limit contacts
Measuring medium:
Air or non-aggressive gases
Measuring principle:
Electromechanical diaphragm measuring system
Measuring unit:
Pa or m³/h
Smallest measuring range:
0…50 Pa (0.5 mbar), resolution 11 Pa
Largest measuring range:
0…3500 Pa (35 mbar), resolution 11 Pa
Measuring ranges:
0…10 Pa, 0…20 Pa, 0…50 Pa, 0…100 Pa, 0…200 Pa, 0…400 Pa, 0…500 Pa, 0…1000 Pa, 0…2000 Pa, 0…3000 Pa, 0…3500 Pa
Measuring range selection:
factory preset
Characteristics:
linear or square rooted
Damping:
selectable 0, 1, 2, 4, 8, 16, 32 s
Ambient temperature:
-10…+50°C
Storage temperature:
-25…+60°C
Switching function:
min. or max. for each contact
Adjustable switching ranges:
0 … 100% measuring range
Switching outputs:
2 potential-free change-over contacts
Switching delay:
adjustable 0 … 20 s
Contact load:
250 Vac, 6A, induction-free load
Overpressure protection:
min. up to 10-times the measuring range
Static pressure:
max. 0.2 bar
Zero point calibration:
Adjustable by REEDcontact, no cyclic zero-point calibration required
Reaction time:
direct
Zero drift:
±0.75%
Sum of linearity and hysteresis:
±1%
Temperature drift zero point:
±0.3% / 10K
Temperature drift measuring range:
±0.2% / 10K
Housing:
Ultramid/ABS, black / grey
Dimensions:
122 x 120 x 85 mm (w x h x d)
Weight:
approx. 900 g
Protection class:
IP65 according EN 60529
Display:
Illuminated LCD display – 4 lines, 20 characters
Electrical connections:
Screw terminals, cable entry: 3 x M16 x 1.5
Pressure connections:
Hose connections 8 mm ø
Power supply:
230 Vac, 24 Vac or 24 Vdc
Power consumption:
approx. 1.5 VA
Output:
0/2…10 V and 0/4…20 mA
EMC:
EN 61000-6-2, EN 61000-6-3, CE-mark
RoHS:
According RoHS-directive 2011/65/EU