DIFFERENTIAL PRESSURE MANOMETER DA2000-S

Differential pressure manometer in a protective housing

Diaphragm element
Smallest measuring range 0…100 Pa
Wide 270° analog display – scale length ca. 250 mm
No supply voltage needed
Scaling in m3/h possible
Protection class IP 66

Manometer with diaphragm element for indication of pressure, under pressure or differential pressure of non aggressive gas. The Manometer is delivered with accessories for mounting in front or behind a panel or wall installation.
Optional are:

  • Two limit value pointers red or green
  • Manometer with analog output signal
  • Combination of indicator and pressure switch fitted in a wall mounting bracket

Operating mode:
Measuring mode
Measuring medium:
Air or non-aggressive gases
Measuring principle:
Electromechanical diaphragm measuring system
Measuring unit:
Pa
Smallest measuring range:
0…100 Pa (1 mbar)
Largest measuring range:
0…5000 Pa (50 mbar)

Measuring range:
0…100 Pa (1 mbar), 0…200 Pa (2 mbar), 0…500 Pa (5 mbar), 0…1000 Pa (10 mbar), 0…2000 Pa (20 mbar), 0…5000 Pa (50 mbar)
Measuring range selection:
factory preset
Ambient temperature:
-10…+50°C
Storage temperature:
-25…+60°C

Overpressure protection:
min. up to 10-times the measuring range

Static pressure:
max. 0.2 bar

Zero point calibration:
scale fine adjustment via screw

Reaction time:
direct

Zero drift:
±0.75%

Sum of linearity and hysteresis:
± 2 % of measuring range

Temperature drift zero point:
±0.3% / 10K

Temperature drift measuring range:
±0.2% / 10K

Housing:
Ultramid/ABS, transparent cover

Dimensions:
164 x 194 x 110 mm (w x h x d)

Weight:
approx. 1460 g

Protection class:
IP66 according EN 60529

Display:
pointer display with scale

Scaling:
Scale length 270° = ca. 250 mm

Pressure connections:
Hose connections 5 mm ø

EMC:
EN 61000-6-2, EN 61000-6-3, CE-mark
RoHS:
According RoHS-directive 2011/65/EU

Are you interested?

Leave us a message and we will get back to you as soon as possible.