DIFFERENTIAL PRESSURE / VOLUME FLOW CONTROLLER DPC200-R
DIFFERENTIAL PRESSURE / VOLUME FLOW CONTROLLER DPC200-R
Electromechanical diaphragm measuring system
Measuring range from 0…50 Pa (0.5 mbar) up to 0…6000 Pa (60 mbar)
Alphanumeric LCD-display
Analogue output 0…10 V
Relay alarm output for measuring and control mode
Selectable measurements (differential pressure or volume flow)
Selectable units (metric or imperial)
Adjustable k-factor for volume flow calculation
Controlling mode or measuring mode selectable
Measuring mode with adjustable limit value
Supply voltage 20…30 Vdc; 24 Vac (+/-15%)
Compact plastic housing IP 54
Control mode with adjustable:
2 setpoints
PI parameters for PI algorithm
maximum output voltage
control action: positive / heat or negative / cool
GRILLO-DPC differential pressure controllers / volume flow controllers are used to measure and control low differential pressures of non-aggressive gases, especially air. A signal of 0…10V is available to the user as an analog output. Depending on the setting of the device, this signal has different meanings. If the instrument is used as a pressure sensor, the output signal is proportional to the measured pressure. As a volume flow sensor, the device provides a root-equipped output signal. In pressure or flow rate control, the output signal represents the manipulated variable of the PI control.
It is used, for example, in air conditioning technology for controlling fans, monitoring room pressure or controlling filters. In addition to the analogue output, an additional alarm output (open collector) is available for limit value monitoring or filter monitoring.
Data_sheet_DPC200_serie
Operation manuals – DPC200-R
Operating mode:
Measuring mode or control mode
Measuring medium:
Air or non-aggressive gases
Measuring principle:
Electromechanical diaphragm measuring system
Measuring unit:
Pa / inH2O or m3/h or cfm
Smallest measuring range:
0…50 Pa (0.5 mbar) / 0.2 InH20
Largest measuring range:
0…6000 Pa (60 mbar) / 24 InH20
Measuring range:
0…50 Pa (0.5 mbar), 0…100 Pa (1 mbar), 0…500 Pa (5 mbar), 0…1000 Pa
(10 mbar), 0…2000 Pa (20 mbar), 0…4000 Pa (40 mbar), 0…6000 Pa (60 mbar)
Measuring range selection:
Factory preset
Adjustable controlling parameters:
P/I – parameter, k-factor, maximum output voltage, normal/ inverse control
Characteristic:
linear for pressure measurement, radiated for volume flow measurement
Ambient temperature:
-10…+50°C
Storage temperature:
-25…+60°C
Control characteristic:
PI – algorithm
Setpoint settings:
2 setpoints can be set via keys, selection of setpoints via potential free contact
Limit signal Output / alarm output:
Relay 250 Vac / 10 A
Alarm delay time:
Freely adjustable in the range of 0 … 60 seconds – 2 … 15 minutes
Overpressure protection:
0.2 bar
Static pressure:
max. 0.2 bar
Zero point calibration:
Adjustable by REEDcontact, no cyclic zero-point calibration required
Reaction time:
direct
Zero drift:
±0.75%
Sum of linearity and hysteresis:
± 0.5 % … ± 1 %
Temperature drift zero point:
±0.3% / 10K
Temperature drift measuring range:
±0.2% / 10K
Housing:
UL 94 HB; Ultramid with hinged lid of ABS
Dimensions:
95 x 70 x 54 mm (w x h x d)
Weight:
approx. 250g
Protection class:
IP54 according EN60529
Display:
Two-line alphanumeric LCD display, 2 x 16 characters
Electrical connections:
Cable entry M16x1.5, screw terminals, electronics protected against incorrect polarity
Cable entry:
2 x M16
Pressure connections:
Hose connections 5 mm ø and 6 mm ø
Operational position:
Vertical, position dependence when rotated through 90 ° approx. 25 Pa
Power supply:
10…30 Vdc; 24 Vac (±15%)
Power consumption:
approx. 10 mA @ 10 Vdc, ca. 12 mA @ 24 Vdc
Output:
0…10 V (Imax = 0.4 mA @ 10 Vdc, Imax = 2 mA @ 20 Vdc)
EMC:
EN 61000-6-2, EN 61000-6-3, CE-mark
RoHS:
According RoHS-directive 2011/65/EU